Análisis del sistema de alarmas del EMS del CENACE

Análisis del sistema de alarmas del EMS del CENACE




Section
TECNOLÓGICOS E INNOVACIÓN

How to Cite
Análisis del sistema de alarmas del EMS del CENACE. (2014). Revista Técnica "energía", 10(1), PP. 191-199. https://doi.org/10.37116/revistaenergia.v10.n1.2014.115

Dimensions
PlumX

How to Cite

Análisis del sistema de alarmas del EMS del CENACE. (2014). Revista Técnica "energía", 10(1), PP. 191-199. https://doi.org/10.37116/revistaenergia.v10.n1.2014.115

Download Citation

W.P. Gamboa
C.S. Erazo

Similar Articles

1-10 of 470

You may also start an advanced similarity search for this article.

The purpose of this article is to investigate regulations related to alarm system use and management, in order to perform a comparison with the CENACE’s EMS alarm system. Regulations EEMUA 191 and ANSI/ISA-18.2 recommend methodologies for alarm management and provide referential performance indexes. In order to calculate such indexes, a statistical analysis of CENACE alarms was performed over a period of 30 days and upon comparison with recommended indexes, it was determined that the CENACE’s EMS alarms were not within the aforementioned recommended limits. Therefore, certain suggestions were proposed for reducing the number of deployed alarms and thus meet the good engineering practices recommended by the referenced regulations.